RX2 MODBUS WITH CP1

Modified on Thu, 27 Mar, 2025 at 9:02 AM

 

 

Introduction

This document describes the procedure to configure and connect a CP1[] series PLC to an RX2 inverter drive for simple motion control using Modbus RTU. This example is intended for a new CP1/RX2 user and illustrates easy programming and configuration for simple inverter motion control of a new system.A screenshot of a computer

AI-generated content may be incorrect.

 

 

 

By default, the RX2 is set to accept speed reference and run command signals from the built-in front panel keypad and external digital input signals. In order for the RX2 to be controlled entirely over Modbus, the following parameters (AA101and AA111 highlighted in yellow, below) must be changed. Please be sure to cycle the power to the inverter after changing these parameters in order for the new settings to take effect. The sample CX-Programmer project uses Modbus settings of 9,600bps (baud rate), 8 data bits, 1 stop bit and no parity, and also assumes that the RX2 has a node number (network address) of 1. Therefore, no other parameters need to be changed from the defaults, as they already match these settings.

 


 

A close-up of a data

AI-generated content may be incorrect.

A white and black document with text

AI-generated content may be incorrect.

A white rectangular object with a black border

AI-generated content may be incorrect.


A screenshot of a computer

AI-generated content may be incorrect.

 

 

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article