What Power Supply Should Be Used For ES2-THB Temperature/Humidity Sensors And ES2-HB Humidity Sensors?

Modified on Sun, 11 May, 2025 at 10:24 PM

A 24-VDC power supply with a maximum ripple voltage of 2% p-p.
See whether the 24 VDC Output Power Supply Unit can be used for your application.
ES2-THB and ES2-HB consume less than 10 mA of current.
Select a Power Supply Unit with sufficient capacity for the number of Sensors connected.

 
Example:
S8VS-01524 Switch Mode Power Supplies (Input: 100 to 240 VAC, Output: 24 VDC, 0.65 A)
S82K-00324 Switch Mode Power Supplies (Input: 100 to 240 VAC, Output: 24 VDC, 0.13 A)
 