The status of the control output depends on the type of Temperature Sensors and the type of error.
| Temperature Sensor type | Temperature Sensor error | Control output |
| Thermocouple input | Burnout | OFF |
| Short-circuit | ON if the set point is higher that the temperature at the shorted section, OFF if it is lower. |
|
| Resistance thermometer | Burnout of element or lead wire A | OFF |
| Burnout of lead wire B | ON | |
| Burnout of lead wire A, B, and B (all three wires) | ON | |
| Short-circuit of element, lead wires A and B | ON | |
| Short-circuit of lead wires B and B | Normal control but there is an error | |
| Thermistor input | Burnout | ON |
| Short-circuit | OFF |
There is no way of sending notification of an input error to E5C2. Check the inputs if abnormal operation is detected.