I'm Using General-Purpose 61F Floatless Level Controllers With Cable Conductor Of 2 mm2 And A Length That Is Less Than 1 km, But It Malfunctions. Is There A Solution For This?

Modified on Sun, 11 May, 2025 at 10:20 PM

It's possible that the cable conductor diameter is too large. Try changing to 0.75-mm2 conductor, or replace 61F with a long-distance model.

*Stray capacitance increases with thick cable diameters, which shortens the applicable cable length.
 