The Threshold Value Cannot Be Set. What Is Causing This, And What Can Be Done To Resolve It?

Modified on Sun, 11 May, 2025 at 10:41 PM

Cause 1:

The HIGH threshold value is set lower than the LOW threshold value.
In this case, the following error message will be displayed.



Remedy 1:

Make sure that the HIGH threshold value is set higher than the LOW threshold value.

Cause 2:

The hysteresis (Hys) is too high. If this is the case, the difference between the HIGH threshold value and the LOW threshold value is smaller than the hysteresis value, so that a PASS judgment is not possible. The setting is thus not allowed.

Remedy 2:

Make the hysteresis value smaller to avoid the condition described above.
 