My 8-Second ON-Delay Timer Program That Uses A TIM Instruction Does Not Run Properly. What Is The Problem?

Modified on Sun, 11 May, 2025 at 10:39 PM

The Problem Ladder Program
 
8 second ON-delay
TIM instruction in diagram 1 has a timer setting of 80. To set an 8-second timer, this value must be changed to
#0080
(8.0 seconds).
If the timer setting value is set to 80, then the contents of CIO 80 when TIM0001 is executed will be used as the set time.
 