Why Does X-Linker Control Linked To A Numerical Value Write Different Values? - CX-Server Lite version 1.1/OPC version 1.1

Modified on Sun, 11 May, 2025 at 10:09 PM

When using the text box and a CX-Linker control linked to a numerical value, it appears to write values that are different to those that are entered.

This is because the Excel TextBox is designed for text, and sends the ASCII value for the numerical value that is entered. For example, if you enter 5 in the textbox the value 53 will be written to the PLC. There is no workaround to this since you can't set the datatype of the text box to numerical. 




 

Related Products
CX-Server Lite 1.0 and CX-Server OPC 1.1

 

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article