Sometimes when you try to create and run a CX-Supervisor runtime application, you can be presented with the following error:
"Access To The CX-Server Project Has Been Denied. The Project File Is Either Set To Read Only Or Is Invalid"
This error is caused by CX-Supervisor being unable to write to the CX-Server project file (.cdm) which could be the result of an ungraceful exit of CX-Supervisor (maybe using 'end task' from task manager) or the file being set to read only.
You should close all Omron software and kill CX-Server processes in task manager, these may be some or all of the following:
- cdmsvr20.exe
- cxdbms.exe
- cxsdi_portman.exe
Now ensure that the files in the CX-Supervisor project folder are all set to read/write.