CIMR-V7AZB0P40 is rated 3.0A (200V Single Phase) at 10kHz Carrier Frequency.
If you change the setting to 14kHz, the maximum allowed continous output current is 2,6A (87% derating). So if your actual continous output current is between 2.7A-2.9A, we recommend using CIMR-V7AZB0P70.
If you change the setting to 14kHz, the maximum allowed continous output current is 2,6A (87% derating). So if your actual continous output current is between 2.7A-2.9A, we recommend using CIMR-V7AZB0P70.