What Is The Difference Between Methods To Use A Terminating Resistor Attached To The T-branch Tap Or A Terminal Block Style Terminating Resistor Of The DeviceNet?

Modified on Sun, 11 May, 2025 at 10:13 PM

It differs by whether the T-branch Tap "DCN1-1C" and/or "DCN1-3C" is located within 6m or more than 6m far from a node of the main line.

If it is located within 6m from a node of the main line, a supplied terminating resistor can be attached to the T-branch Tap.

If it is located more than 6m far from a node of the main line, a terminating resistor must be attached to the end of the node.

In this case, the T-branch Tap fitted with a terminating resistor or the Terminal Block style terminating resistor DRST-1 must be connected. The maximum cable length between the node and the terminating resistor is 1m.
 
 